Tool

Voltage drop calculator

Built for engineers who need a fast design check, a clearer conductor-sizing decision, and a result they can review without hunting through separate tables.

NEC-guided design targets Single-phase, three-phase, and DC Minimum conductor sizing

Built for practice

3% Typical branch or feeder design target
5% Typical combined feeder plus branch target
NEC Notes 210.19 and 215.2 mention 3% segment and 5% total-path guidance

Design basis

Set the circuit objective and electrical conditions.

Start with the segment you are checking, then enter the known load, system voltage, and one-way conductor length.

Objective - Default target - Formula basis -

Conductor model

Choose the conductor for the run.

Preset sizes cover common building-wire checks for copper and aluminum conductors.

The calculator uses the selected insulation temperature rating for resistance and base ampacity checks.

Base ampacity - Resistance @ rating - Parallel path -

Method notes

Calculation notes.

NEC design guidance

Use 3% as a typical branch or feeder target and 5% for the combined path to the farthest outlet. Confirm the final requirement with the project code edition and AHJ.

Voltage-drop method

The result uses conductor resistance, one-way length, load current, material, insulation rating, and system type.

Base ampacity only

Preset ampacity values are base references before ambient correction, conductor-count adjustment, rooftop effects, and terminal limits.

Engineer review triggers

Recheck long motor feeders, nonlinear loads, and parallel runs when field conditions require manufacturer data or a full engineering review.

Reference basis

  • NFPA 70 voltage-drop informational guidance for feeders and branch circuits
  • Southwire Power Cable Manual conductor property and AC/DC voltage-drop equations
  • Common NEC ampacity table values used for base conductor sizing checks